Acrel DTSD1352 three phase smart energy meter for solar inverter
Shape |
Standard function |
Optional |
|
Meteing:Active KWh (Positive And Negative),Reactive KWh (Positive And Negative),A. B, C Phase Positive Active Energy Measurement:U、I,P、Q、S、PF、F2~31ST Voltage And Current Harmonic Pulse Output:Active Pulse Output, Reactive Pulse Output, Clock Pulse Output |
C:One Channel RS485(Modbus-Rtu) |
F:Multi-Tariff |
||
T:Temperature Monitoring |
||
K:Switch(1DI+1DO) |
General
FUNCTIONS
-
CommunicationRS485(Modbus-RTU)Rated U and IAC 3×100V, 3×380V, 3×57.7/100V, 3×220/380V; 3×1(6)A, 3×10(80)AAccuracykWh: Class 0.5S,kVarh:Class 2Frequency50/60HZ(Optional),range: 45~65HZDisplay8 digits LCD display U, I, P, Q, PF, kWh and other energy consumption, Power measure (999999.99kWh)Pulse outputPulse output kWh/kvarh
- Consumption<10VA(Single phase)InstallationDIN 35mmDimension(L*W*H)126.5*88*69.5mmSwitch relayMagnetic latching relay(ADL3000-E build-in)Clock≤0.5s/dStarting currentDirect connect: 0.004IbConnect via CT: 0.001ln
TECHNICAL PARAMETERS
Voltage |
Reference Voltage |
3*57.7/100V,3*220/380V,3*100V,3*380V |
Reference Frequency |
50Hz |
|
Consumption |
<10VA(Single Phase) |
|
Current |
Maximum Current |
6A,80A |
Starting Current |
Direct Connect:0.004lb Connect Via:0.001ln |
|
Consumption |
<1VA(Single Phase Rated Current) |
|
Measurement Performance |
Accuracy |
Class 0.5 |
Standards Compliant |
IEC 62053-22:2003 |
|
Pulse |
Pulse Width |
80+20ms |
Pulse Constant |
400imp/KWh 6400imp/KWh |
|
Communication |
Interface |
RS485 |
Protocol |
Mod Bus-RTU |
|
Temperature Range |
Work |
-25℃~55℃ |
Storage |
-40℃~70℃ |
|
Humidity |
≤95%(No Condensation) |
|
Altitude |
<2000m |
LCD DISPLAY
FRONT PANEL
- ① Seal for Anti theft② Brand③ Panel④ Enter-wire⑤ Auxiliary function⑥ Pulse output light⑦ Button⑧ Outlet wire
DIMENSION & INSTALLATION
NETWORK
By INvengo TO KNOW MORE ABOUT INVENGO RFID, PLEASE CONTACT US!
Our experts will solve them in no time.