0102030405
Acrel AGF-MXXT DC1500V Multi-channel Monitoring Device
Scenario Application Project

Characteristics
◆ Primary current is connected in through perforation. Easy installation, high safety.
◆ With Hall sensor, the max isolation measuring current 20A
◆ Voltage measurement range for Bus bar is up to DC1.5kV
◆ LED display, fit for checking and testing operation in wide-temperature or outside environment.
◆ With the function of inner temperature measurement for real-time measurement of the inner temperature of combiner box
◆ With RS485 Modbus RTU
◆ More options of power supply
◆ Compatible with din rail installation and baseboard fixation installation, small dimension savingmorebox space.
FUNCTIONS
◆ Photovoltaic cell open circuit alarm to cooperate with group string voltage and judge Comprehensively
◆ With 3-channel switching state monitoring to collect output idle contact information of DCbreaker 、lightning protector. protector etc
◆ Option RS485 port, Modbus-RTU protocol; programmable slave address, baud rate, dataformat
◆ English LCD display,convenient to set parameters and check the data
Multi-circuits Measurement up to 24 DC Circuits
● Input Channel: up to 24 Circuits ● LED Indicator for Re-flux, Disconnection, Over-current ● Rated Current: 20A ● Accuracy: 0.5 Class ● Voltage Measuring Range: up to 1500V (Busbar) |
![]() |
3-Channel DI Switch Status Monitoring
● DI Status of Lightning Protector and DC CB ● Octocoupler or dry Contact |
![]() |
Keypads HMI for Programming
● Communication(address, baud rate and etc.) ● Over-temp Alarm Threshold |
![]() |
TECHNICAL PARAMETERS
Item |
AGF-M4T |
AGF-M8T |
AGF-M12T |
AGF-M16T |
AGF-M20T |
AGF-M24T |
Input channels |
4 |
8 |
12 |
16 |
20 |
24 |
Rated current |
DC 0~20A | |||||
Response time |
1s | |||||
Accuracy |
0.5 class | |||||
Temperature coefficient |
400ppm | |||||
RS485 communication |
RS485/ModBus-RTU protocol,4800/9600/19200/38400bps | |||||
Additional function |
||||||
Switch input |
3-way input(optocoupler or dry contact mode) | |||||
General technical parameters |
||||||
Temperature/ Humidity |
Working temperature: -35~+65℃, humidity95%,no condensation, no corrosion gas place *Display module work temperature:-20~+70℃ | |||||
Temperature measurement function |
To measure the inner temperature of box (-20℃~100℃) | |||||
Altitude |
≤3000m | |||||
Insulation resistance |
≥100MΩ | |||||
Industrial frequency withstand voltage |
power/communication/switching input/cell voltage input--AC 2kV/1min (When the auxiliary power supply is DC1500V, the withstand voltage between the power supply, photocell input and other circuit is AC 2.7kV) Current input/power、cell voltage 、communication、switching state—AC3.5kV/1min | |||||
EMC |
GB_T 17626.2-2006; Electrostatic discharge immunity test 3rd grade, air discharge 8kV, contact discharge 6kV. | |||||
GB_T 17626.4-2008; Electrical fast transient immunity test grade 4, common mode 4kV, difference mode 2kV | ||||||
GB_T 17626.5-2008; Surge(shock) immunity test grade 4, common mode 4kV, difference mode 2kV | ||||||
GB_T 17626.8-2006; Power frequency magnetic field immunity test grade 4 |
WIRING

Note: The arrow shows current direction. Wrong connection will lead to abnormal operation of the device.
DIMENSION & INSTALLATION
-----Power supply module size
-----Power supply module size

Note: Imaginary line is the fixing size of the bottom plate
As power supply module is heavy, bottom plate is needed in installation to avoid its coming off during transportation.
----8-channel confluence acquisition module installation dimension

---4-channel confluence acquisition module installation dimension

NETWORK


AGF-T Perforation type PV confluence acquisition device

CE Certificate-1 of AGF-MxxT Series

CE Certificate-2 of AGF-MxxT Series

EMC Certificate of AGF-MxxT Series

LVD Certificate of AGF-MxxT Series
By INvengo TO KNOW MORE ABOUT INVENGO RFID, PLEASE CONTACT US!
Our experts will solve them in no time.