Acrel AMC16(L)-DETT Multi-circuit DC48V Energy Meter
Scenario Application Project



FUNCTIONS
Multi-circuit Metering
● Up to 6-circuit DC circuit monitoring ● Rated Voltage [DC]: -48Vdc ● Rated Current [DC]: 5Vdc [via hall sensor] ● 1 extra Utility Voltage Monitoring [via -/5Vdc transducer] |
![]() |
Wired Communications
● 1-way RS485 Interface ● MODBUS-RTU Protocol ● Baud Rate: 9600 default [optional 1200, 2400, 4800] ● Wiring Cable Recommend: RVSP 2x1.5²mm |
![]() |
Extra Power Output ● Applicatrion: ±12Vdc Power Output for 6 paired Hall Sensors ● Output Specs: +12V/100mA, -12V/50mA |
![]() |
TECHNICAL PARAMETERS
Technical parameter |
Index |
|
input |
DC rated voltage |
1 channel: -48VDC |
DC current |
6 channels hall sensors output is 5V,current ratio can be set according to the actual ratio | |
Commercial power monitoring |
1 channel: 0-5VDC | |
Overload capacity |
Voltage:1.2times continued,2 times continued 1s; Current: 1.2 times continued,10 times continued 1s. | |
Accuracy (superposition hall sensors) | 1%In≤I≤10%In error±2.5%; I>10%In error±2% | |
Measurement resolution | Voltage output accuracy 0.01V; current output accuracy 0.01A; power output accuracy 0.01kw; energy output accuracy 0.01kwh. | |
functions | Basic function | Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication. |
Metering function | Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts. Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change. | |
Alarm function | DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm,memory failure alarm, AC input power failure alarm | |
Timing function | support broadcast timing, could remote timing to the meter through RS485 communication. | |
Communication |
Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or custmized |
Hall sensor power supply | Power supply output:+12V/100mA, -12V/50mA | ||
Clock accuracy | ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃), | ||
Auxiliary power supply | Voltage range | -40V~-60VDC | |
Power consumption | Whole device≤2W( no hall power supply output) | ||
Storage |
It has the storage function of historical power data and historical alarm information, and the memory is 2MB | ||
Insulation resistance | ≥40MΩ | ||
environment | Temperature | Working : -20℃~+60℃; storage:-40℃~+70℃ | |
Humidity | ≤98% no condensation, no corrosive gas place | ||
Altitude |
≤4000m | ||
Protection level |
IP20 | ||
Material flame retardent | Terminal glow wire temperature 960℃±10℃ ,shell glow wire temperature 650℃±15℃ | ||
installation |
Standard 35mm din rail | ||
Lightning protection | Voltage input (differential mode) | Peak value 5kA | |
Auxiliary power supply (differential mode) | Peak value 5kA |
WIRING

Note: arrow direction should be the same with current direction marked on the sensor .

DIMENSION & INSTALLATION

NETWORK


AMC16(L)-DETT DC power meter module of base station

CE Certificate of AMC16(L)-DETT Series

IEC61010-1 Testing Report of AMC16(L)-DETT Series

Telecom Base Station IOT Energy Monitoring Solution [Local or to 3rd party]

Test Report of AMC16(L)-DETT Series