ASCB1-63-C63 3P Three Phase Smart Circuit Breaker
picture |
standard |
optional |
ASCB1-63-C16 3P |
●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;
●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
●Type C tripping curve, guide rail installation;
●The rated current of the monitorable circuit is 16A; number of poles: 3 pole. ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.
|
None |
picture |
standard |
optional |
ASCB1-63-C32 3P |
●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;
●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
●Type C tripping curve, guide rail installation;
●The rated current of the monitorable circuit is 32A; number of poles: 3 pole. ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.
|
None |
picture |
standard |
optional |
ASCB1-63-C63 3P |
●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;
●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
●Type C tripping curve, guide rail installation;
●The rated current of the monitorable circuit is 63A; number of poles: 3 pole. ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.
|
None |
Appearance
ASCB1-63-C-1P
|
Length
|
Width
|
Height
|
Pole
|
Phase
|
Wires
|
|
Parameter(mm)
|
109
|
72
|
75.5
|
3
|
three
|
3
|
Parameters
Model
|
ASCB1-63
|
ASCB1LE-63
|
||
Pole
|
1P/2P/3P/4P
|
2P/4P
|
||
Grade of Shell
|
63A
|
|||
Rated Voltage
|
230V(1P/2P)、400V(3P/4P)
|
|||
Rated Current
|
6A,10A,16A,20A,25A,32A,40A,50A,63A
|
|||
Instantaneous Unbuckle Type
|
C/D
|
|||
Rated Short-circuit Breaking Capacity
|
6000A
|
|||
Protect
|
Over-current Protection
|
Default 100% rated current alert,
110% Rated current trip with adjustable threshold
|
||
Short-circuit Protection
|
5-10 Rated current for 0.04 seconds for circuit break protection
|
|||
Overload Protection
|
Default 100% rated power alert,110% Rated power trip with adjustable threshold
|
|||
Over-voltage Protection
|
Default 110% rated voltage alert,120% rated voltage trip with adjustable threshold
|
|||
Under-voltage Protection
|
Default 90% rated voltage alert,80% rated voltage trip with adjustable threshold
|
|||
Over-temperature Protection
|
Default 80℃ alert,100℃ trip, the threshold is adjustable
|
|||
Leakage Protection
|
No
|
Default 20mA alert, 30mA trip, the threshold is adjustable
|
||
Leakage self-Inspection
|
No
|
Manual button self-inspection
|
||
Mechanical Life
|
20000 times
|
|||
Electrical Life
|
6000 times
|
|||
Levels of Protection
|
IP20
|
|||
Connection Capacity
|
1-35mm²
|
|||
Elevation Requirements
|
2000m
|
|||
Ambient Temperature
|
-10℃~55℃,the average temperature at 24h was no higher than 40℃
|
|||
Environmental Requirements
|
No explosion hazard, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibration
|
|||
Relative Humidity
|
At + 40℃, the relative humidity of the air is 50% and can have high relative humidity at lower temperatures
|
|||
Storage Temperature
|
-20℃-70℃
|
|||
Class of Pollution
|
Ⅱ
|
|||
Installation Type
|
Ⅲ
|
|||
Way to Installation
|
Standard 35mm guide rail installation
|
Function
ASCB1 Series Intelligent MCB Function
|
||||
ASCB1-63
|
· Can monitor voltage, current, power, power and temperature in real time
· with overpressure, underpressure, overload, short circuit, overcurrent, and overtemperature and other protection functions
· With local manual lever, local electric control, local lock, remote control, timing control and other control function
· Guide rail type installation, optional pole number 1P / 2P / 3P / 4P
· Standard RS-485 (MODBUS) communication; optional buckle curve type C / D
|
Wiring
- Step1: Connect the RS485 port on the gateway to the BUS port of the circuit breaker by using the communication cable provided by the gateway
- Step2: Insert the barbed side of the connecting wire of the circuit breaker into the external terminal of the previous circuit breaker toward the outside of the terminal, and the colors need to be matched one by one.
Typical Connection
FAQ
Q: Can the circuit breaker data be collected through RS485 communication?
A: The circuit breaker has its own RS485 communication interface, and it does not need to be equipped with an ASCB1-M gateway to access the customer system, but the customer needs to provide the circuit breaker with DC12V 12A auxiliary power supply
Q: How many circuit breakers can a gateway carry?
A: 16PCS
Q: How Gateways and Circuit Breakers are Networked?
A: The gateway and the circuit breaker are connected by a 4pin cable, a set of DC12V auxiliary power supply, and a set of RS485 communication lines.
The connection between the circuit breaker and the circuit breaker is the same.
One-key addressing operation through the gateway
Q: Does the circuit breaker need to be equipped with additional accessories?
A: 1. Internally integrate various sensor modules, including: current sensor, leakage transformer, temperature sensor, etc.;
2. The circuit breaker integrates the release function, which can realize remote opening and closing operations;
3. Configure the circuit breaker network cable