ADW210 Multi Circuits three phase Energy Meter
picture | standard | optional |
ADW210-D10 paired 5A CT |
Measurement of all electric parameters of N(1,2,3,4) channels of 3-phase circuits. External current transformers. 1.3-phase voltage, current, zero-sequence current, frequency; 2.3-phase power, total power(active, reactive, apparent); 3.Three phase power factor, overall power factor; 4.Voltage and current phase angle, voltage and current imbalance; 5.Voltage, current total harmonic and 2nd-31st harmonic; 6.Record of extreme values of voltage, current and power in current month and last month; 7.Maximum current, power demand and real-time current, power demand; 8.200 event records, recording the action of DI/DO; 9.support over-voltage, over-current, phase failure, DI linkage and other alarm output; 10.The rate of 4 time zones and 14 time periods can be set; 11.Four quadrant electric energy, 12-month multi rate electric energy statistics; 12.31 days four quadrant and multi tariff electric energy freezing 13.Active energy accuracy class 1.0, and reactive electric energy accuracy class 2.0; 14.Standard function: 2DI/2DO, RS485, 1 way active pulse output (corresponding circuit can be switched). |
1S |
2S | ||
3S | ||
4S | ||
ADW210-D16 paired 100A CT | 1S | |
2S | ||
3S | ||
4S | ||
ADW210-D24 paired 400A CT | 1S | |
2S | ||
3S | ||
4S | ||
ADW210-D24 paired 600A CT | 1S | |
2S | ||
3S | ||
4S |
GENERAL
FUNCTIONS
Accuracy
Active power: Class 1
Reactive power: Class 2
Frequency
Range: 50 - 60Hz
Pulse output
Active pulse output and reactive pulse output
Consumption
<0.5VA(Single phase)
Dimension (L*W*H)
Panel size (L×W): 72*97.7*36 mm
Installation: Din 35mm
Wireless
Transmission on 470MHz and maximum distance in open space is 1km; 2G; NB
Starting current: 4‰lb
Technical Parameters
Auxiliary power |
AC/DC 85~265V; Consumption≤10VA; |
|
Input |
Frequency |
45~65Hz; |
Voltage |
AC 3×220V/380V; Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; Power consumption: ≤ 0.5VA; |
|
Current |
AC 5A、100A、400A、600A;(External opening transformer); Power consumption: ≤ 0.5VA; Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s; |
|
Measurement accuracy |
Frequency 0.05Hz, voltage、current Class 0.5; 2-31st harmonic accuracy: ± 1%; Active electric energy level 1, reactive electric energy level 2; |
|
Features |
Pulse output |
Output mode: optocoupler pulse with open collector; |
Communication |
RS485、Modbus-RTU; Baud rate 1200~38400; |
|
Switching Input |
Dry contact input、Built in power supply; |
|
Switching Output |
Output mode: Relay normally open contact output; contact rating: AC 250V/3A DC 30V/3A; |
Optional Module
External Module (MTL)
12 External NTC Temp. Measurement
4 Channels Residual Current MeasurementExternal Wireless Module(AWT100)
Downlink RS485; Uplink 4G, 2G, NB, Lora, LoraWAN, Ethernet, WiFi, GPS, ProfibusExternal Module(MK)
12 Channels DI + 4 Channels DO
Dimension
Main part dimension(L×W×H): 87.8*72*71.5mm
35mm Din rail installation; Tolerance: ±1mmModule dimension(L×W×H): 87.8*36*71.5mm
35mm Din rail installation; Tolerance: ±1mm
Current Transformer Matched with ADW2xx Series |
Dimension(mm) |
Perforation size (mm) |
|||||
W |
H |
D |
M |
N |
φ1 |
φ2 |
|
AKH-0.66/K-∅ 10N |
27 |
44 |
32 |
25 |
36 |
10 |
9 |
AKH-0.66/K-∅ 16N |
31 |
50 |
36 |
27 |
42 |
16 |
17 |
AKH-0.66/K-∅ 24N |
39 |
71 |
46 |
36 |
52 |
24 |
23.5 |
AKH-0.66/K-∅ 36N |
42.5 |
82 |
58 |
40 |
56 |
36 |
35 |
Picture of Current Transformer |
Installation
Wiring
① U / Pulse / DO / DI / Communication / Auxiliary Power Supply
② Brand
③ Panel
④ Model Number
⑤ CH1, CH2, CH3, CH4 for current / extension module interface
⑥ Button
⑦ Infrared Status
⑧ Pulse Output Light
Network
PACKAGE
MINIMUM PACKAGE |
||||
MINIMUM PACKAGE |
Package Dimension(1 PC) 170*150*130mm |
Package Weight(1 PC) 0.245Kg |
||
WHOLE BOX PACKAGE |
Package Dimension(36 PCS) 540*530*480mm |
Package Weight(36 PCS) 10.5kG |
||
PRODUCT HS CODE |
9028301400 |
ATTENTION !
The above packing and weight data are only refer to model ADW210.