• Phone
  • E-mail
  • Whatsapp
  • Whatsapp
    cf541b0e-1eed-4f16-ab78-5cb5ce535649s3e
  • Leave Your Message

    ASCB1-63-C16 1P Smart Circuit Breaker

    Products

    Products Categories
    Featured Products

    ASCB1-63-C16 1P Smart Circuit Breaker

    ● Model:ASCB1-63-C16-1P ASCB1-63-C32-1P ASCB1-63-C1663-1P

    ●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;

    ●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;

    ●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;

    ●Type C tripping curve, guide rail installation;

    ●The rated current of the monitorable circuit is 16A; number of poles: 1 pole.

    ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.

      picture

      standard

      optional

      asdzxcxz1vxj

      ASCB1-63-C16 1P

      ●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
      ●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;
      ●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
      ●Type C tripping curve, guide rail installation;
      ●The rated current of the monitorable circuit is 16A; number of poles: 1 pole.                                                    ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.

      None

       

      picture

      standard

      optional

      asdzxcxz2axs

      ASCB1-63-C32 1P

      ●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
      ●Has multiple protection functions such as overvoltage, undervoltage, overload, short circuit, overcurrent and overtemperature;
      ●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
      ●Type C tripping curve, guide rail installation;
      ●The rated current of the monitorable circuit is 32A; number of poles: 1 pole.
      ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.

      None

       

      picture

      standard

      optional

      asdzxcxz3ogu

      ASCB1-63-C63 1P

      ●Can monitor parameters such as voltage, current, power, electric energy and temperature in real time;
      ●Has multiple protection functions such asovervoltage,undervoltage, overload, short circuit, overcurrent and overtemperature;
      ●With local manual push rod, local electric control, local locking, remote control, timing control and other control functions;
      ●Type C tripping curve, guide rail installation;
      ●The rated current of the monitorable circuit is 63A; number of poles: 1 pole.
      ●Standard configuration of RS485 (MODBUS) communication, used in conjunction with intelligent gateway.

      None

      Appearance

      • asdzxc3ki4
      • asdzxc17r7
      • asdzxc29c0
      ASCB1-63-C-1P
      Length
      Width
      Height
      Pole
      Phase
      Wires
      Parameter(mm)
      109
      36
      75.5
      1
      single
      1

      Parameters

      Model
      ASCB1-63
      ASCB1LE-63
      Pole
      1P/2P/3P/4P
      2P/4P
      Grade of Shell
      63A
      Rated Voltage
      230V(1P/2P)、400V(3P/4P)
      Rated Current
      6A,10A,16A,20A,25A,32A,40A,50A,63A
      Instantaneous Unbuckle Type
      C/D
      Rated Short-circuit Breaking Capacity
      6000A
      Protect
      Over-current Protection
      Default 100% rated current alert,
      110% Rated current trip with adjustable threshold
      Short-circuit Protection
      5-10 Rated current for 0.04 seconds for circuit break protection
      Overload Protection
      Default 100% rated power alert,110% Rated power trip with adjustable threshold
      Over-voltage Protection
      Default 110% rated voltage alert,120% rated voltage trip with adjustable threshold
      Under-voltage Protection
      Default 90% rated voltage alert,80% rated voltage trip with adjustable threshold
      Over-temperature Protection
      Default 80℃ alert,100℃ trip, the threshold is adjustable
      Leakage Protection
      No
      Default 20mA alert, 30mA trip, the threshold is adjustable
      Leakage self-Inspection
      No
      Manual button self-inspection
      Mechanical Life
      20000 times
      Electrical Life
      6000 times
      Levels of Protection
      IP20
      Connection Capacity
      1-35mm²
      Elevation Requirements
      2000m
      Ambient Temperature
      -10℃~55℃,the average temperature at 24h was no higher than 40℃
      Environmental Requirements
      No explosion hazard, no conductive dust, no sufficient corrosion of metal and damaged insulation, no significant vibration
      Relative Humidity
      At + 40℃, the relative humidity of the air is 50% and can have high relative humidity at lower temperatures
      Storage Temperature
      -20℃-70℃
      Class of Pollution
      Installation Type
      Way to Installation
      Standard 35mm guide rail installation

      Function

      ASCB1 Series Intelligent MCB Function
      ASCB1-63
      · Can monitor voltage, current, power, power and temperature in real time
      · with overpressure, underpressure, overload, short circuit, overcurrent, and overtemperature and other protection functions
      · With local manual lever, local electric control, local lock, remote control, timing control and other control function
      · Guide rail type installation, optional pole number 1P / 2P / 3P / 4P
      · Standard RS-485 (MODBUS) communication; optional buckle curve type C / D

      Wiring

      3bf348fad95f87db243d1f12b0cf6394hvc
      • baa6f32798e291cb6d135daf1d51e6b58beStep1: Connect the RS485 port on the gateway to the BUS port of the circuit breaker by using the communication cable provided by the gateway
      • b69caabba25b31673ba1884f0705b92155cStep2: Insert the barbed side of the connecting wire of the circuit breaker into the external terminal of the previous circuit breaker toward the outside of the terminal, and the colors need to be matched one by one.
      9e059dc9c43565767259cb904965ece6pwv

      Typical Connection

      e1789892503af7c3eff3d2725a781583p2w

      FAQ

      Q: Can the circuit breaker data be collected through RS485 communication?

      A: The circuit breaker has its own RS485 communication interface, and it does not need to be equipped with an ASCB1-M gateway to access the customer system, but the customer needs to provide the circuit breaker with DC12V 12A auxiliary power supply

      Q: How many circuit breakers can a gateway carry?

      A: 16PCS

      Q: How Gateways and Circuit Breakers are Networked?

      A: The gateway and the circuit breaker are connected by a 4pin cable, a set of DC12V auxiliary power supply, and a set of RS485 communication lines.
      The connection between the circuit breaker and the circuit breaker is the same.
      One-key addressing operation through the gateway

      Q: Does the circuit breaker need to be equipped with additional accessories?

      A: 1. Internally integrate various sensor modules, including: current sensor, leakage transformer, temperature sensor, etc.;
      2. The circuit breaker integrates the release function, which can realize remote opening and closing operations;
      3. Configure the circuit breaker network cable

      pdf (4)ns0
      ASCB1-63
      pdf (4)ns0
      ASCB1LE-63
      pdf (4)ns0
      ASCB1第三方检测报告
      pdf (4)ns0
      ASCB1强制性认证产品符合性自我声明
      pdf (4)ns0
      S591 ManualofASCB1SeriesofIntelligentMicro-CircuitBreakersV1.00

      Leave Your Message