ADL3000-E-A/KC UL Three Phase Energy Meter
GENERAL
FUNCTIONS
Communication
RS485(Modbus-RTU)
Rated U and I
AC 3×100V, 3×380V, 3×57.7/100V, 3×220/380V; 3×1(6)A, 3×10(80)A
Accuracy
kWh: Class 0.5S,kVarh:Class 2
Frequency
50/60HZ(Optional),range: 45~65HZ
Display
8 digits LCD display U, I, P, Q, PF, kWh and other energy consumption, Power measure (999999.99kWh)
Pulse output
Pulse output kWh/kvarh
Consumption
<10VA(Single phase)
Installation
DIN 35mm
Dimension(L*W*H)
126.5*88*69.5mm
Switch relay
Magnetic latching relay(ADL3000-E build-in)
Clock
≤0.5s/d
Starting current
Direct connect: 0.004Ib
Connect via CT: 0.001ln
TECHNICAL PARAMETERS
Voltage |
Referencevoltage |
3*57.7/100V,3*220/380V,3*100V,3*380V |
||
Referencefrequency |
50Hz |
|||
Consumption |
<10VA(Single phase) |
|||
Current |
Maximum current |
6A,80A |
||
Starting current |
Direct connect:0.004lb Connect via:0.001ln |
|||
Consumption |
<1VA(Single phase rated current) |
|||
Measurement performance |
Accuracy |
Class 0.5 |
||
Standards compliant |
IEC 62053-22:2003 |
|||
Pulse |
Pulse width |
80+20ms |
||
Pulse constant |
400imp/kWh 6400imp/kWh |
|||
Communication |
Interface |
RS485 |
||
Protocol |
Mod bus-RTU |
|||
Temperature range |
Work |
-25℃~55℃ |
||
Storage |
-40℃~70℃ |
|||
Humidity |
≤95%(No condensation) |
|||
Altitude |
<2000m |
LCD Display
Wiring
Dimension & Installation
Network
FAQ
Q:I bought a three-phase four-wire meter, can it be wired as three-phase three-wire?
A:Yes, press the key to set the meter to three-phase three-wire mode.
Q:What is the difference between ordinary secondary access and -CT (model external transformer)?
A:Ordinary secondary meter could access the ratio XXX/5(1)A of the CTs which could be actual current on site, the -CT model comes with an external transformer will be convenient for installation(It cannot be disassembled, otherwise it will burn the meter). There are CTs available on site to facilitate with No stitch removal.
Q:What are 3*100V、3*57.7/100V、3*380V、3*220/380V?
A:3*100V, 3*57.7/100V are used for high voltage, used in conjunction with voltage transformers, where 3*100V represents 3P3W,3*57.7V/100V represents 3P4W; 3*380V, 3*220V/380V are used for low voltage, direct voltage input, among them3*380V represents 3P3W, 3*220V/380V represents 3P4W.
Q:Can this meter communicate with PLC?
A:Yes, only need PLC to support RS485 interface, Modbus RTU or DL/T645 protocol.
PACKAGE
MINIMUM PACKAGE |
|
|
|
|
MINIMUM PACKAGE |
Package dimensions(1 PC) 170*150*130mm |
Net Weight(1 PC) 0.254KG |
||
WHOLE BOX PACKAGE |
Package dimensions(36 PCS) 540*530*480mm |
Package Weight(36 PCS) 11.836KG |
||
PRODUCT HS CODE |
9028301400 |