    ● Rated Current: AC0.1-10(80)A

    ● Rated Voltage: AC3x230V/400V

    ● RS485(MODBUS-RTU) Communication

    ● 12 digits LCD Display; 35mm DIN Rail Installation

    ● Energy Accuracy:kWh Class C

    ● MID Certificated

      picture standard optional

      ADL400-D xpn

      ADL400

      Meteing:Active kWh (positive and negative),Reactive kWh (positive and negative), A. B, C phase positive active energy

      Measurement:U、I,P、Q、S、PF、F2~31ST Voltage and current harmonicPulse output:Active pulse output

      C:RS485(Modbus-rtu)
      F:Multi-tariff

      GENERAL

      ADL400 din rail energy meter adopts DIN35mm din rail installation with LCD display,it can measure electric parameters and has energy pulse output, RS485 communication,which has the advantages of small size, high precision, good reliability and convenient installation.

      FUNCTIONS

      b5351b21e4d21c1158e3cb10c1c231695h747b10e137a04a7d39a7e0801eaa153dfpuf

      TECHNICAL PARAMETERS

      Voltage

      Nominal voltage

      AC3x230V/400V

      Nominal frequency

       45~65Hz

      consumption

      <10VA

      Current

      Maximum current

      0.1-10(80)A

      Starting current

      0.01A

      Consumption

      <1VA

      Measurement performance

      Accuracy

      kWh Class C

      Range

      0~9999999999.99kWh

      Clock

      accuracy

      Error ≤0.5s/d

      Active pulse

      width

      80±20ms

      constant

      1000imp/kWh,10000imp/kWh

      Communication

      Interface

      RS485

      Protocol

      MODBUS-RTU

      Temperature range

      Work

      -25℃~55℃

      Storage

      -40℃~70℃

      Humidity

      ≤95%(No condensation)

      Altitude

      <2000m

      DISPLAY

      6265cb66b00f7f9d0ce4e2d7baf44114l2c

      FRONT PANEL

      ADL400-D MID Three Phase Energy Meterhg7

      NETWORK

      Network8qe

      INSTALLATION

      ADL400-D MID Three Phase Energy Meter (2)6mk

      FAQ

      Q:After the meter is powered on, the power or energy count is inaccurate.
      A:Switch the meter display to the power (active power P, power factor λ) interface, and check whether the power display is negative or not. And whether the power factor is between 0.9-0.95, and then check whether the incoming and outgoing wires of the current signal wire are connected reversely (that is, the current The incoming wire must be the same as the incoming wire end of the instrument) and consistent with the wiring diagram on the instrument.

      Q:The instrument cannot communicate with the host computer normally after power on.
      A:1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V;
      2. Check whether the communication wiring method is correctly wired in accordance with the wiring diagram requirements (that is, the communication terminal A/B of the corresponding to communication serial port A/B); 

      PACKAGE

      MINIMUM PACKAGE

      MINIMUM PACKAGE (4)0n0

      MINIMUM PACKAGE (1)1t0

      MINIMUM PACKAGE (3)gec

      MINIMUM PACKAGE (2)78o

      MINIMUM PAKAGE

      Package dimensions(1 PC)

      170*150*130mm

      Pakage Weight(1 PC)

      0.5Kg

      WHOLE BOX PAKAGE

      Package dimensions(36 PCS)

      450*240*250mm

      Pakage Weight(36 PCS)

      18.5kG

      PRODUCT HS CODE

      9028301400

      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter CE-EMC Certificate
      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter CE-LVD Certificate
      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter CE-MID Certificate
      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter Installation instruction V1.3
      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter UKCA-EMC Certificate
      pdf (4)ns0
      Acrel ADL400 Three Phase Smart Electricity Meter UKCA-LVD Certificate

      Leave Your Message