AMC48L-AI Single phase Ammeter Analyzer
GENERAL
Parameters
Communication
RS485(Modbus-RTU)
Display
LCD display, set multiplying power
Rated U & I
AC current: AC1A, 5A
Accuracy
Active energy: Class 0.5
Installation
Panel mounted
Dimension(L*W*H)
Panel size (L×W): 48*48mm
Cutout(L×W): 45*45mm
Depth (H): 93mm
Consumption
Current: Power consumption< 0.5VA;
Auxiliary power supply: power consumption≤5VA
Auxiliary power supply
AC 220V
Technical Datasheet
Technical Parameter | Value | |
Input |
Rated Value |
Single phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; |
Overload |
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second |
|
Frequency | 45Hz~65Hz |
|
Power Consumption | Power consumption of each voltage,current input circuit is less than 0.5VA |
|
Accuracy | Class 0.5 | |
Function |
Display | LED or LCD |
Communication |
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc. |
|
Alarm | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. |
|
Analog |
DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) |
|
Switching |
Input:4 channel or 2 channel dry contact Input,built in power supply Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC |
|
Auxiliary Supply | AC/DC 85-265V |
|
Power Consumption | <5VA |
|
Insulation resistance |
≥ 100MΩ |
|
Power frequency withstand voltage |
Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV |
|
Environment |
Temperature | Operation: -10℃~+55℃Storage: -25°C ~+70°C |
Humidity | ≤95%RH,no condensation,without corrosive gas |
|
Altitude | ≤ 2500m |
Dimension
Wiring
Network
Installation
FAQ
Q: No display on power?
A: Check whether the supply voltage is within the operating voltage range.
Q: Incorrect reading of voltage,current, electricty, etc?
A: Checking that the voltage/current ratio setting are correct;
Checking whether the wiring mode setting is consistent with the actual situation;
Checking whether the voltage transformer and current transformer are in good condition.
Q: Abnormal communication
A: Check whether the adress,baud rate,check bits in the communication;
Setting are consistent with the host computer;
Check whether the RS485 converter is normal;
Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.
PACKAGE
MINIMUM PACKAGE |
||||
MINIMUM PACKAGE |
Package Dimension(1 PC) 170*150*130mm |
Pakage Weight(1 PC) 0.62Kg |
||
WHOLE BOX PACKAGE |
Package dimensions(36 PCS) 450*245*250mm |
Pakage Weight(36 PCS) 3.66KG |
||
PRODUCT HS CODE |
9028301400 |
ATTENTION !
The above packing and weight data are only refer to model AMC48-AI.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!
Introducing the AMC48L-AI Single Phase Ammeter Analyzer, the sophisticated tool designed to provide precise and comprehensive analysis of single-phase electrical systems. This state-of-the-art device offers advanced features and accurate measurement capabilities, making it an essential instrument for a wide range of applications.Equipped with advanced AI technology, the AMC48L-AI Ammeter Analyzer delivers precise and reliable measurements of key electrical parameters such as voltage, current, power factor, frequency, and energy consumption. Its high-resolution display and user-friendly interface make it easy to monitor and analyze power usage in real-time, allowing for efficient optimization and cost savings.The AMC48L-AI is designed with convenience and usability in mind, offering an intuitive interface and a range of connectivity options, including USB and Bluetooth, for easy data transfer and analysis. Its lightweight and portable design ensure versatility and ease of use in various settings, from industrial facilities to residential applications.Furthermore, the AMC48L-AI is built with a focus on durability and accuracy, ensuring consistent and reliable operation even in demanding environments. Its compliance with international standards guarantees its suitability for use in diverse regions and applications.In summary, the AMC48L-AI Single Phase Ammeter Analyzer is the ultimate solution for precise and convenient analysis of single-phase electrical systems. With its advanced AI technology, comprehensive measurements, and user-friendly design, the AMC48L-AI empowers users to effectively manage and optimize their electrical systems with confidence and ease. Whether for industrial, commercial, or residential use, the AMC48L-AI sets a new standard for single-phase ammeter analysis.