AMC48L-AV Single phase Volmeter Analyzer

GENERAL
Parameters
Communication
RS485(Modbus-RTU)
Display
LCD display, set multiplying power
Rated U & I
Single phaseAC 100V, 400V
Accuracy
Active energy: Class 0.5
Installation
Panel mounted

Dimension(L*W*H)
Panel size (L×W): 48*48mm
Cutout(L×W): 45*45mm
Depth (H): 93mm
Consumption
Current: Power consumption< 0.5VA;
Auxiliary power supply: power consumption≤5VA
Auxiliary power supply
AC 220V

Technical Datasheet
Technical Parameter | Value | |
Input |
Rated Value |
AC voltage:Single phaseAC 100V, 400V Three phaseAC 100V, 400V, 660V(UL-L, Only 72/ 96) |
Overload |
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second |
|
Frequency | 45Hz~65Hz |
|
Power Consumption | Power consumption of each voltage, current input circuit is less than 0.5VA |
|
Accuracy | Class 0.5 | |
Function |
Display | LED or LCD |
Communication |
RS485, Modbus-RTU protocol;(1 start bit, 8 data bit, 1 stop bit, no parity) Baud Rate 2400/4800/9600/19200 bps etc. |
|
Alarm | 1 channel passive relay, contact capacity 3A/30VDC, 3A/250VAC, Used for high, low, unbalance alarm etc. |
|
Analog |
DC4~20mA, ( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) |
|
Switching |
Input:4 channel or 2 channel dry contact Input, built in power supply Output:2 channel switching output, NO relay contact, capacity:3A/30VDC, 3A/250VAC |
|
Auxiliary Supply | AC/DC 85-265V |
|
Power Consumption | <5VA |
|
Insulation resistance |
≥ 100MΩ |
|
Power frequency withstand voltage |
Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV |
|
Environment |
Temperature | Operation: -10℃~+55℃Storage: -25°C ~+70°C |
Humidity | ≤95%RH, no condensation, without corrosive gas |
|
Altitude | ≤ 2500m |
Dimension

Wiring

Network

Installation

FAQ
Q: No display on power?
A: Check whether the supply voltage is within the operating voltage range.
Q: Incorrect reading of voltage,current, electricty, etc?
A: Checking that the voltage/current ratio setting are correct;
Checking whether the wiring mode setting is consistent with the actual situation;
Checking whether the voltage transformer and current transformer are in good condition.
Q: Abnormal communication
A: Check whether the adress,baud rate,check bits in the communication;
Setting are consistent with the host computer;
Check whether the RS485 converter is normal;
Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.
PACKAGE
MINIMUM PACKAGE |
![]() |
![]() |
![]() |
![]() |
MINIMUM PACKAGE |
Package Dimension(1 PC) 170*150*130mm |
Pakage Weight(1 PC) 0.62Kg |
||
WHOLE BOX PACKAGE |
Package dimensions(36 PCS) 450*245*250mm |
Pakage Weight(36 PCS) 3.66KG |
||
PRODUCT HS CODE |
9028301400 |
ATTENTION !
The above packing and weight data are only refer to model AMC48-AI.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!
Introducing the AMC48L-AV Single Phase Voltmeter Analyzer, the cutting-edge solution for accurate and comprehensive analysis of single-phase electrical systems. This state-of-the-art device offers advanced features and precise measurement capabilities, making it an indispensable tool for a wide range of applications.The AMC48L-AV is designed to provide accurate and reliable measurements of voltage in single-phase electrical systems, enabling users to monitor and analyze voltage levels with confidence and precision. Equipped with a high-resolution display and user-friendly interface, the analyzer makes it easy to visualize and interpret voltage data, empowering users to make informed decisions about power usage and optimization.With its advanced technology and intuitive design, the AMC48L-AV ensures seamless operation and efficient analysis of voltage parameters. Whether used in industrial, commercial, or residential settings, the analyzer offers versatility and convenience, helping users to monitor electrical systems with ease and accuracy.In addition to its advanced measurement capabilities, the AMC48L-AV is built to withstand demanding environments, offering durability and reliability in all operating conditions. Its compliance with international standards further underscores its suitability for use in diverse regions and applications, providing users with confidence and peace of mind.Furthermore, the AMC48L-AV is designed with portability and ease of use in mind, featuring a lightweight and compact design for effortless transportation and deployment. Its connectivity options, including USB and Bluetooth, allow for seamless data transfer and analysis, ensuring seamless integration into existing workflows.In summary, the AMC48L-AV Single Phase Voltmeter Analyzer sets a new standard for precision and convenience in single-phase voltage analysis. With its advanced technology, user-friendly interface, and robust design, the AMC48L-AV offers an unparalleled solution for monitoring and analyzing voltage parameters in a wide variety of electrical systems, making it an essential tool for professionals across industries.