APM520 series 3-phase Multifunction Power Meter
picture | standard | optional | optional group |
APM520 |
Full electric parameter measurement (I, U, kW, kvar, kWh, kvarh, Hz, cos); four-quadrant electric energy, split-phase electric energy, apparent electric energy; real-time demand and maximum demand; electric parameter extreme value and last month Monthly extremevalue; voltage and current unbalance; voltage and current phase angle; total harmonic and 2nd-63rd subharmonic; voltage crest factor, telephone waveform factor, current K coefficient, vector diagram, voltage and current waveform; last 128 pcs of DIDO Records; the latest 128 pcs of alarm records ; default switch communication 4DI2D02EP1C; |
1.K(2DI2DO) | 1+2+3+4+5 4+5+6+11+12 4+5+7+11+12 4+5+8+11+12 4+5+9+11+12 4+5+10+11+12 |
2.2M(2 channel analog) | |||
3.2C(The second RS485) | |||
4.F(Multi tariff) | |||
5.S(Class 0.2S+fault recording) | |||
6.WF(WiFi) | |||
7.LR(Lora) | |||
8.CE(Ethernet) | |||
9.4G(4G communication) | |||
10.NB(NB communication) | |||
11.T(Temperature measurement) | |||
12.L(Residual current measurement) |
GENERAL
FUNCTIONS
Accuracy
Voltage、current and power: Class 0.2
Active power: Class 0.5; Reactive power: Class 1
Pulse Output
Output mode: photocoupler pulse with open collector;
Pulse constant: 10000imp/kWh (default)
Consumption
Voltage、current: Power consumption: <0.5VA;
Auxiliary power supply: Power consumption ≤15VA
Starting Current: 0.1%
Installation: Panel mounted
Frequency: Range: 45-65Hz
Relay: 3A/AC250V, 3A/DC30V
Dimension (L*W*H)
Panel size (L×W): 96*96mm
Cut-out size (L×W): 88*88mm
Auxiliary Power Supply
AC/DC 85V~265V or AC/DC 115~415V
Display
Front Panel
① Type of Parameters
② Load Value
③ Total Power
④ DO Status Indicator
⑤ Menu
⑥ Key Down
⑦ Data Display
⑧ Navbar
⑨ DI Status Indicator
⑩ Enter Button
⑪ Key up
Wiring
Network
Installation
Application
FAQ
Q: What’s the storage capacity, storage format and data storage interval of SD card?
A: The meter is equiped with standard 4G SD card while saving the data of electrical parameter, energy, event, SOE, alarm. Also, the setting of storage interval could be changed. (1 min interval for electrical parameter and 1 hour interval for energy) .
Q: How should I select the expanded modules of APM5xx?
A: Our users can select 3 of the optional modules at will even repeatly except for communication module. Also, the order of module installation could be random.
Q: The features of APM5xx?
A: Except for wave record and flicker record function, 0.2S measuring accuracy can also be a option. Also, users can measure the data through browser by using Ethernet auto WEB.
Q: As for the auxiliary power supply of APM5xx?
A: AC/DC 85~265V or 115~415V is both optional. Also, 380V line voltage can also serve as power supply.
PACKAGE
MINIMUM PACKAGE |
||||
MINIMUM PAKAGE |
Package dimensions(1 PC) 170*150*130mm |
Net Weight(1 PC) 0.78KG |
||
WHOLE BOX PAKAGE |
Package dimensions(36 PCS) 540*530*480mm |
Package Weight(36 PCS) 15.2kG |
||
PRODUCT HS CODE |
9028301400 |
ATTENTION !
The above packing and weight data are only refer to model APM520.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!