    Multi-channel Energy Meter in PV Power Distribution System in the Netherlands

    Acrel Projects

    Multi-channel Energy Meter in PV Power Distribution System in the Netherlands

    2024-01-23

    1.Background

    As the global fossil energy (oil and coal) is approaching exhaustion, pollution is becoming more and more serious, and the climate is warming, etc., many countries and regions around the world have successively issued regulations and policies, which have promoted the development of the PV industry.

    However, due to the large number and concentration of the PV monitoring circuits, a large number of power distribution room space is occupied.

    Acrel multi-channel energy meter has a high level of integration. A single module can monitor 48 circuits, and at the same time, it can also be matched with switch acquisition module to realize the circuit monitoring of PV system.



    2.Project Brief

    One PV system company in the Netherlands that provides PV systems for a wide variety of buildings.

    In the PV monitoring system of the customer, the current situation of more than 300 loops need to be monitored at the same time. These loops are centrally in the distribution room. In order to collect information more effectively, the customer chooses the product of AMC16Z-FAK48, so as to complete the monitoring of the circuit without adding cabinets.



    3.Product introduction

    AMC16Z series multi-loop acquisition module

    AC Networking Solution


    Ac incoming module

    AMC16Z-ZA

    A+B 2 channels:

    The busbar voltage, current, active power, reactive power, power factor, active power, reactive power, 2-63 harmonics of the total three-phase inlet line,

    Neutral line current, zero ground voltage, 6DI2DO, 2 channels leakage, 1 channel temperature and humidity, 1 channel RS485 communication

    It is equipped with DC24V voltage output to power the shunt module and touch screen



    Ac outgoing switch & electrical parameter module

    AMC16Z-FAK24

    AMC16Z-FAK48

    A+B 2 channels:

    Three-phase outgoing voltage, 24/48 single-phase current, active power, reactive power, power factor, active power, reactive power, 2-31 harmonics,

    24/48 active switching input,

    1 channel RS485 communication

    Ac outgoing switch quantity acquisition module

    AMC16Z-KA(active)

    AMC16Z-KD(passive)

    A+B 2 channels:

    Two 24-channel outgoing switch acquisition,

    1 channel RS485 communication

    Ac outgoing electrical parameters acquisition module

    AMC16Z-FA

    A+B 2 channels:

    Two 12-way outlet electric parameter collection,

    1 channel RS485 communication


    DC Networking Solution

    DC Inlet Module

    AMC16Z-ZD

    A+B 2 channels:

    The bus voltage, current, power and active electric energy of the total incoming line,

    6DI2DO, 1 channel temperature and humidity, 1 channel RS485 communication,

    It is equipped with DC24V voltage output to power the shunt module and touch screen.

    With 2 ±12V voltage output, power supply to hall sensor on main road

    Branch DC outlet module

    AMC16Z-FDK24

    AMC16Z-FDK48

    A+B 2 channels:

    Outgoing circuit voltage, 24/48 one-sided current, power, electric energy,

    24/48 active switching input,

    1 channel RS485 communication

    DC output electrical parameters acquisition module

    AMC16Z-FD

    A+B 2 channels:

    Two 12-way outlet electric parameter collection,

    1 channel RS485 communication

    DC insulation monitoring module

    AMC16Z-ZJY

    Monitor the bus voltage, bus voltage to ground and bus insulation state of A+B double-channel DC feed circuit. One line of RS485 interface is used to connect to touch screen or RS485 hub. Meanwhile, six RS485 interfaces are equipped for external digital leakage current sensor, which can measure up to 192 branches.



    4.Networking Solution

    AC Networking Solution


    DC Networking Solution


    5.Installation



    Bibliography

    1、Solutions for enterprise micro-grid system